Provide an optimal lighting environment
Rationale: A layered, flexible, and low-flicker artificial lighting setup that can adjust to individual occupant needs and day-to-day weather conditions reduces the risk of developing eye strain and migraines, and helps regulate circadian rhythm, which has strong positive effects on mood, sleep, and the immune system.
Requirements
Demonstrate compliance with the below:
Optimal Lighting Environment (Full Credit):
Demonstrate compliance with all of the following requirements:
- Ensure that 51% of lighting fixtures within all regularly occupied spaces within the building(s) are dimmable and/or tunable.
-
- Qualifying regularly occupied spaces must include but are not limited to the following:
-
- Workspaces: which include workstations, flexible workspaces, individual offices, and circulation between workstations. Note that hallways, corridors, and elevator banks are not considered regularly occupied spaces.
- Common spaces and amenities: which include spaces where occupants can gather to work, eat, take breaks, or meet — such as meeting rooms, lounge or break areas, multipurpose rooms, resource centers, fitness facilities, exercise rooms, lactation rooms, quiet rooms, and reception areas.
-
- Qualifying regularly occupied spaces must include but are not limited to the following:
-
- Ensure that the dimmable and/or tunable lighting fixtures can be operated by all building(s) occupants.
- Ensure that all luminaires within all regularly occupied areas of the building(s) through one of the following:
-
- luminaires are classified with Unified Glare Rating (UGR) of 19 or lower.
- luminance does not exceed 6,000 cd/m2 at any angle between 45 and 90 degrees
- emit light above the horizontal plane
-
- Provide a minimum of one type of the following qualifying ambient lighting sources for general illumination throughout all regularly occupied areas within the building(s):
-
- ceiling-mounted
- recessed ceiling fixtures
- wall sconces
- floor lamps
- cove lighting.
-
- Ensure that all luminaires and their controls within all regularly occupied spaces within the building(s) are low flicker that meet one of the following:
-
- comply with Pst LM ≤ 1.0 and SVM ≤ 0.4 at full load.
- are tested according to the requirements in Joint Appendix JA-10 and classified as “reduced flicker operation” by California Title 24.
- align with IEEE Std 1789-2015 recommended practices 1, 2, or 3 and have a flicker of no less than 90Hz and a modulation percent ≤ 0.08*fflicker.
-
- Provide a minimum of one type of the following qualifying task lighting at 51% of all regularly occupied workstations within the building(s):
-
- track lighting
- pendants
- desk and table lamps
- under-cabinet lighting
- luminous partitions.
-
Compliance Documentation
Design Pathway
Option 1:
Requirement 1
-
-
Upload design drawings or product specifications of each unique dimmable/tunable light fixture.
-
Checkbox to confirm that a minimum of 51% of all lighting fixtures within all regularly occupied spaces within the building(s) will be dimmable/tunable light fixtures.
-
Requirement 2
-
-
Upload design drawings or product specifications of each unique dimmable/tunable light fixture showing how it can be operated by all building(s) occupants.
-
Checkbox to confirm that the dimmable/tunable light fixtures that will be installed can be operated by all building occupants.
-
Requirement 3
- Upload design drawings or product specifications of each unique luminaire showing how it will reduce glare.
Requirement 4
-
-
Upload design drawings or product specifications of the type of ambient lighting for general illumination that will be provided.
-
Requirement 5
-
-
Upload luminaire product specifications or datasheets of each unique type of low flicker luminaire that will be used showing the low-flicker technical details.
- Checkbox to confirm that all luminaires and their controls within all regularly occupied spaces within the building(s) will be low flicker.
-
Requirement 6
- Upload design drawings or specifications of each unique type of qualifying task lighting that will be provided at workstations.
- Text box to input the number of regularly occupied workstations within the building
- Text box to input the number of regularly occupied workstations within the building that will include qualifying task lighting
Built Pathway
Option 1:
Requirement 1
-
-
Upload an annotated photograph(s) or product specifications of each unique dimmable/tunable light fixture.
-
Checkbox to confirm that a minimum of 51% of all lighting fixtures within all regularly occupied spaces within the building(s) are dimmable/tunable light fixtures.
-
Requirement 2
-
-
Upload an annotated photograph(s) or product specifications of each unique dimmable/tunable light fixture showing how it can be operated by all building(s) occupants.
-
Checkbox to confirm that the dimmable/tunable light fixtures can be operated by all building occupants.
-
Requirement 3
-
- Upload design drawings or product specifications of each unique luminaire showing how it reduces glare.
Requirement 4
-
-
Upload design drawings or product specifications of the type of ambient lighting for general illumination that are provided.
-
Requirement 5
- Upload luminaire product specifications or datasheets of each unique type of low flicker luminaire that are used showing the low-flicker technical details.
- Checkbox to confirm that all luminaires and their controls within all regularly occupied spaces within the building(s) are low flicker.
Requirement 6
- Upload an annotated photograph(s) or specifications of each unique type of qualifying task lighting that are provided at workstations.
- Text box to input the number of regularly occupied workstations within the building
- Text box to input the number of regularly occupied workstations within the building that include qualifying task lighting